The Lightning Protection Characteristics of ±800 kV Yunnan – Guangdong UHVDC Transmission Line

何金良
DOI: https://doi.org/10.3969/j.issn.1674-0629.2013.01.005
2013-01-01
Abstract:Lightning is one of the main causes of transmission lines trip-outs.Aiming to solve the lightning protection problem of ±800 kV Yunnan – Guangdong HVDC transmission line,this paper calculates and analyzes the lightning protection characteristics of the line by analyzing the parameters of the line,investigating the lightning activity along the line and building a calculation method based on the advanced leader progression model.Firstly,the lightning activities in the passing areas are investigated as to have the proper corresponding lightning day values.Then,the influences of ground slope,insulation strength and cross-valley depth on the shielding failure characteristic,the impacts of tower height and grounding resistance on the lightning direct striking characteristic are analyzed,and the lightning trip-out rates of each segment of the line are achieved by considering the impact of topography.Finally,some proper lightning protection measures such as for reducing grounding resistance and decreasing the protection angle are discussed.