Study on Phase-order Arrangement of 750 Kv Double Circuit Transmission Line in Same Tower

张赟,曾嵘,张波
DOI: https://doi.org/10.3969/j.issn.1673-7598.2008.06.002
2008-01-01
Abstract:The phase-order arrangement of double circuit transmission line has comparatively great effect upon electromagnetic enviroment and lightning performance.By taking 750 kV Lanzhoudong-Pingliang double circuit transmission line as example,the parameters to be considered in design are calculated under different phase-order arrangement of double circuit transmission line with vertical-arranged circuit,such as conductor surface field strength,ground electric field,radio interference,audible noise,corona loss and counterattack trip rate.The results show that the electromagnetic environment is best and corona loss is lowest under ABC/ABC and ABC/BAC arrangement,while counterattack trip rate of double circuit transmission line under ABC/ABC,ABC/ACB arrangement is much higher than that under other phase-order arrangements.Therefore for improving electromagnetic environment,reducing corona loss,improving lightning performance,it is suggested to adopt ABC/BAC phase-order arrangement when constructing double circuit transmission line with vertical-arranged circuit.