Comparative Study on Measures to Limit Load-Rejection Opening Overvoltage of Long-Distance and Large-Capacity UHVAC Transmission Lines

LI Yang,ZHOU Hao,SHEN Yang,SUN Ke
DOI: https://doi.org/10.13335/j.1000-3673.pst.2013.12.041
2013-01-01
Abstract:Based on the model of long-distance and large-capacity UHVAC line with double-end source, two different methods are used to limit overvoltage and the economical evaluation of the two methods are given. One of them is increasing the number of average subsections of transmission line, namely the overvoltage is limited by only adopting metal oxide arrester (MOA) and HV shunt reactor when opening and closing resistors are not used, and the another one is to limit load-rejection opening overvoltage by adding opening and closing resistors to circuit breakers. Simulation results show that the maximum difference of opening overvoltage levels by the two limiting measures is about 0.04 p.u., so the effects of limiting overvoltage by the two methods are basically the same. Through the measure of increasing subsection number of transmission line the load-rejection opening overvoltage under single-phase earth fault can be limited, however the number of required switching stations is more, so the investment cost is high;through adding opening and closing resistors the same purpose of effectively limiting the overvoltage by lesser subsection number of transmission line can be achieved, meanwhile the number of switching stations can be reduced due to decreasing of the number of subsections of transmission line, so hundreds of millions RMB can be saved, and even the highest saved investment cost may be up to 1 billion RMB. Study results also show that the best value of opening resistor is within the range from 600Ωto 700Ω, thus to limit load-rejection overvoltage it is suitable for long-distance and large-capacity transmission lines to add opening and closing resistors.
What problem does this paper attempt to address?