Research on Overvoltage Characteristics and Influencing Factors of Converter Station under Grounding Fault
Zongyang Zhang,Zhiyuan Wang,Chao Kang,Fang Yu,Zixin Ma,Jie Guo
DOI: https://doi.org/10.1016/j.egyr.2022.01.231
IF: 5.2
2022-01-01
Energy Reports
Abstract:In grounding fault of DC system, overvoltage will appear on equipment nodes in converter station. Due to different operation mode and equipment type, it is very different from overvoltage in AC system. Based on Shanghaimiao–Linyi ±800kV Ultra High Voltage Direct Current (UHVDC) transmission project, this paper studies the converter station overvoltage characteristics under the conditions of DC pole line grounding, DC bus grounding and converter transformer valve side grounding fault, then analyzes the influence of smoothing reactor, filter capacitor and grounding pole line on overvoltage. In grounding fault at DC pole line near the converter station, the maximum overvoltage occurs on the inductance of DC filter, which is 592.75kV; In grounding fault at the top of the high voltage converter valve, the maximum overvoltage occurs on the neutral bus, which is 272.17kV. Increasing the inductance or capacitance of the smoothing reactor and filter capacitor, shortening the length of grounding electrode wire can significantly reduce the amplitude and steepness of overvoltage. The calculation results provide a reference for the internal overvoltage suppression of DC converter station with layered access at the inverter side.