Single-phase grounding overvoltage of long-distance UHVAC lines

Yang Li,Yang Shen,Hao Zhou,Rongrong Ji,Ke Sun,Jian Ding,Feng Qian
DOI: https://doi.org/10.3969/j.issn.1006-6047.2013.12.016
2013-01-01
Abstract:The influencing factors of single-phase grounding overvoltage are analyzed and the conditions causing the maximum overvoltage are obtained. With different compensation degrees of HV shunt reactor and different disposals of MOA(Metal Oxide Arrester), the maximum length of UHVAC line is discussed for different segment modes, under which the single-phase grounding overvoltage will not surpass the limitation. The effect of MOA on overvoltage suppression is compared with that of HV shunt reactor, which shows the latter has better effectiveness. For three-segment lines, the maximum total line length may reach 1300 km while that of single segment may reach 500 km. For four-segment and five-segment lines, the maximum total line length may reach 1400 km and 1600 km respectively while that of single segment may reach 400 km.