Research on high-voltage reactor compensation of UHV AC transmission lines

Qiang YI,Hao ZHOU,Rong-rong JI,Qiong-jing XU,Fei SU,Ke SUN,Jia-miao CHEN
DOI: https://doi.org/10.3969/j.issn.1674-3415.2011.20.018
2011-01-01
Abstract:As one of the most important reactive power compensation equipment,the configuration of the high-voltage reactor determines the safety and stability of UHV system.So the application range of high-voltage reactor's compensation mode has been studied.Results show that single-junction compensation mode is suitable for two kinds of lines:the transposed lines only one of whose endpoint throw-off can cause excessive power frequency overvoltage,and transposed lines whose power frequency over-voltage is within the limit but secondary arc current exceeds the limit.Two-junction compensation mode can restrict the power frequency over-voltage caused by load throw-off at both endpoints of line.Sectional compensation can be used in lines more than 550 km in length.The systematic determination of high-voltage reactor compensation program is given and explained with the practical example.This method considers the power frequency overvoltage restriction,and also gives attention to the requirements of the secondary arc limit,no-load voltage controlling,resonance overvoltage prevention,high-voltage reactor standardization,and reactive power balance when transmitting high power is considered.
What problem does this paper attempt to address?