Study on Switching Over-voltage and Its Restrictions in UHVAC System

计荣荣,赵斌才,陈润辉,何川,吴皓,吴哲,周浩
DOI: https://doi.org/10.3969/j.issn.1000-7229.2009.09.008
2009-01-01
Abstract:Based on both domestic and foreign existing study results,and combining PSCAD simulation analysis,this paper studies and discusses the switching over-voltage in UHVAC and its restrictions.Researches show that main attention should be paid on the ground fault,closing and opening over-voltage in UHVAC switching over-voltage.Ground fault over-voltage is relatively lower and can be restricted to allowance by installing arresters at the both ends of line.Closing over-voltage can be suppressed by adopting closing resistor and installing multiple arresters along the line.The former measure has problems of breakdown and damages easily,while the later is verified in EHV system.Opening over-voltage can be restricted by opening resistor and multiple arresters along the line.Considering the inadequacy of opening resistor,it is not suggested for the UHVAC lines in China.
What problem does this paper attempt to address?