Abstract:Combined with a single circuit UHV power transmission project in one million voltage from Jincheng to Jingzhou via Nanyang which is reasoned by State Power Grid Corp. of China, its switching overvoltages, including three-phases closing with no load and single-phase auto-reclosing, are considered. The switching overvoltages are calculated with Electromagnetic Transient Program (EMTDC). The calculation shows that the switching overvoltage is too high up to 1.80 pu if only with parallel resistor in circuit breaker or high performance ZnO arrester. Combining arrester and parallel resistor is a good measure to limit switching overvoltage without such high requirement on arrester's or resister's thermal capacity.