Adding One Group of Arresters to Replace Parallel Resistor in 750kV Transmission Line

Peng-cheng YANG,Shui-ming CHEN,Zong-chuan ZHOU,Shuang ZHANG,Yong-ning HUANG
DOI: https://doi.org/10.13336/j.1003-6520.hve.2008.06.010
2008-01-01
Abstract:How to restrict the switching overvoltage is discussed recently because of the 750 kV transmission line project in Northwest China. Idea of increasing only one group of arrester installed along line replacing with parallel resistance in breakers to suppress switching overvoltage in 750 kV transmission line is realized in this paper. Based on the 750 kV Lanzhoudong-Yinchuandong transmission line project, effects of the arrestor's position on switching overvoltages, including three phases energizing line without load, single phase auto-reclosing are calculated by using the electromagnetic transient program PSCAD/EMTDC. The result shows that without any arresters installed along line, the maximal overvoltage of three phases energizing line with no load (1.94 per unit), single phase auto-reclosing (2.01 per unit) are higher than the design limit value (1.80 per unit). With the help of one arrester installed, along line, the switching overvoltages(the maximal overvoltage of three phases energizing line with no load and single phase auto-reclosing are 1.79 and 1.78 per unit) are acceptable.