Feasibility Of Using One-Column-Varistor Arresters In 1000-Kv Uhv Substations

Jinliang He,Yao Zhou,Zhengqiang Li,Jun Yuan
DOI: https://doi.org/10.1109/TPWRD.2015.2476500
IF: 4.825
2016-01-01
IEEE Transactions on Power Delivery
Abstract:With the application of ultra-high-voltage (UHV) technology, how to reduce the construction cost of the UHV substations is becoming an important and emergent issue. In this paper, two kinds of one-column-varistor arresters are used to replace conventional four-column-varistor arresters for busbars or transformers or both of them. The switching overvoltage and lightning intruding overvoltage are calculated to evaluate the feasibility of using one-column-varistor arresters in UHV substations. At the same time, the energy absorbed by and current flowing through the arresters, and the thermal stability of these one-column-varistor arresters are analyzed to ensure their safe operations. It is shown that conventional one-column-varistor arresters can be used for busbars and transformers in UHV substations to replace conventional four-column-varistor arresters and could highly reduce the construction cost of the UHV substation, but the safety of the substation will remain the same.
What problem does this paper attempt to address?