Calculation Method and Influencing Factors of Overvoltage on Ground Electrode Line on Sending End Caused by Monopolar Fault in UHVDC Transmission System
TENG Yufei,TANG Yong,HUANG Qi,LI Xiaopeng,ZHANG Chun,YAN Lei
DOI: https://doi.org/10.13335/j.1000-3673.pst.2017.0068
2017-01-01
Abstract:Ground electrode line is an important part of UHVDC transmission system, whose operating condition determines reliability of UHVDC transmission system. Calculation method and influencing factors of amplitude and oscillation frequency of overvoltage on ground electrode line at sending end caused by monopolar fault in UHVDC transmission system are studied in this paper. Firstly, transfer function of voltage on ground electrode line head-end under monopolar fault of UHVDC transmission system is investigated. In this function, parameters of primary equipment and DC current control link are both considered. Secondly, based on the transfer function, a method solving amplitude and oscillation frequency of overvoltage is proposed. Finally, validity of the voltage-calculating method is proved using waveform records of a real±800kV UHVDC system in Southwestern area of China. Factors influencing amplitude and oscillation frequency, such as transmission line fault location, ground electrode line length, parameters of current control link and normal DC voltage, are analyzed with a case study.