Influence of zero-sequence mutual inductance of transmission lines of the same passage on equivalent zero-sequence impedance

XU Xi-dong,HUANG Xu-cong,WANG Quan,FANG Yu-dong
DOI: https://doi.org/10.3969/j.issn.1674-3415.2011.04.001
2011-01-01
Abstract:Based on a model of two parallel lines,this paper studies the influence of the overhead earth wire and the adjacent parallel lines on the equivalent zero-sequence impedance of fault line. The influence of such factors as distance between parallel lines,the material of overhead earth wire and the operation condition on the calculation of line equivalent zero-sequence impedance is analyzed. An algorithm of equivalent zero-sequence impedance ,which is based on Carson line model ,is given as well .Finally ,the influences of all factors mentioned above are compared through an example. Theoretical analysis and simulation indicate that the influence of mutual inductance decays with the increase of the distance between lines,a high conductivity overhead earth wire will decrease the equivalent zero-sequence impedance to a certain degree ,and groundingoverhauling of transmission lines of the same passage affects the fault line parameters the most.
What problem does this paper attempt to address?