Characteristics of Resultant Electric Field under Ultra High Voltage Direct Current Test Lines in High Altitude Area
TIAN Feng,YU Zhanqing,ZENG Rong,LI Min,LIU Lei,ZHANG Bo
DOI: https://doi.org/10.3969/j.issn.1003-6520.2013.06.013
2013-01-01
Abstract:In order to obtain characteristics of electromagnetic environment(EME) around UHVDC transmission lines and to provide reliable intelligent support for power line designing,we performed long-term statistical measurements of resultant electric field(ES) on the UHVDC test lines located in National Laboratory for UHV Technology in Kunming,China.The lateral distribution of ES was obtained through synchronous measurements at multiple points under the test lines,and the cumulative probability distribution of ES was acquired based on the results of long-term statistical tests under standard condition.By changing minimum conductor height,pole spacing,and bundle radius,the influences of the line parameters on ES were obtained.Furthermore,the effects of line voltage and polarity on the magnitude and distribution of ES were studied.Conclusions can be drawn that,1) under the regular operating condition,peak values of ES appear at the projection of energized poles,while the negative extremum is larger than the positive one.Compared with bipolar situation,the position where extremum shows is closer to the voltage injecting pole in mono-polar situation;2) in spring,the statistical 50% value of the positive extremum of ES is 19.10 kV/m,while for the negative extremum,it is-25.00 kV/m,however,in fall,these two values are 23.10 kV/m and-21.50 kV/m,respectively,both larger than those in spring;3) as the minimum conductor height,pole spacing,and bundle radius increase,the magnitude of ES decreases;4) the magnitude of ES increases monotonously with the voltage applied on the conductors,and the increasing speeds of bipolar and mono-polar conditions are quite close to each other.