Effect of Reactive Equivalent Fault Impedance on Distance Protection

SHEN Bing,HE Benteng
DOI: https://doi.org/10.3321/j.issn:1000-1026.2006.21.014
2006-01-01
Abstract:Impedance between faulted line and ground is generally regarded as a resistance, but in some cases the equivalent impedance can be reactive. Fault on a transmission line connected to the bus behind the protection is equal to on the bus through a reactive fault impedance. This problem has rarely been noticed. The impedance loci with impedance seen by the protection in this condition is analyzed. The theoretical analysis and digital simulation results show the possibility that distance protection with quadrangular characteristic may mal-operate under this condition.
What problem does this paper attempt to address?