Performance analysis of multiphase compensated distance relay in single-phase-to-ground fault with power swing

Liu Cui,Xinzhou Dong,Shenxing Shi,Bin Wang,Bak Dominik
DOI: https://doi.org/10.13334/j.0258-8013.pcsee.2013.34.028
2013-01-01
Abstract:An impedance relay is the core element of a distance protection, which is widely applied in power systems. Impedance relay's operation can be affected by power swings. Therefore, a power swing blocking element is required to work with, which makes the distance protection scheme more complex. Using the multiphase compensated distance relay as the base, the resultant distance protection can be made insensitive to the power swings and no additional time blocking element is needed. So, it is valuable to analyze the operation characteristics of multiphase compensated distance relays. By analyzing the relay's equation, this paper reported on the performance of the three elements in multiphase compensated distance relays in the case of a single phase to ground fault during power swings. This paper defined the missing operation's area for a faulty phase element and the maloperation's area for a health phase element. The paper also pointed out the disadvantages of the relay working as the protection of II or III section. PSCAD simulation results verified the conclusions. © 2013 Chin. Soc. for Elec. Eng.