Multiphase Compensated Distance Relay Insensitive to Transition Resistances

CUI Liu,DONG Xinzhou
DOI: https://doi.org/10.13334/j.0258-8013.pcsee.2014.19.023
2014-01-01
Abstract:Multiphase compensated distance relay is insensitive to power swing but is highly influenced by transition resistance. In this paper a multiphase compensated distance relay insensitive to transition resistances was proposed. By analyzing the operation equation of multiphase compensated distance relay, a factor was figured out that affected the operation characteristic by transition resistances. The factor can be extracted by introducing zero sequence voltage at the setting point into comparison equation and substituting the fault voltage by the voltage at the end of the protection scope. Using the line impedance angle, and the real part and image part of the factor, the influence by the transition resistance can be eliminated. Based on the above principle, this paper proposed a multiphase compensated distance relay insensitive to transition resistances. The theoretical analysis and simulation results show that the proposed distance relay is insensitive to transition resistances.
What problem does this paper attempt to address?