Distance Protection Principle for Series Compensated Lines Based on the Impedance Angle of the Compensated Point

LIU Shulei,CHEN Fufeng,HE Benteng
2010-01-01
Abstract:Compensated point impedance is defined as the margin of the line impedance between the distance protection relay with the series capacitor and the measured impedance.The impedance angle of the compensated point impedance is between 70° and 90°with fault happened before the series capacitor and is between 90°and 270°with fault occurred after the series capacitor.Accordingly,a new method of fault point recognition is derived.It is integrated with the traditional distance protection to form a new series compensated line distance protection principle.Compared with the voltage-detected program, the new principle obviously increases the distance range of distance protection and effectively solves the steady state overreach problem.This method is verified by simulations using Elector-Magnetic Transient Program.
What problem does this paper attempt to address?