Improved Setting Method of Distance Protection with the SSFCL

LIU Hua-lei,JIANG Dao-zhuo,CHEN Gang,ZHANG Peng-fei
DOI: https://doi.org/10.3321/j.issn:1000-1026.2006.02.017
2006-01-01
Abstract:The fault current limiter (FCL) has certain impact on relaying protection, especially on distance protection, when applied in power systems. This paper studies the effect of the bridge-type solid state fault current limiter (SSFCL) with bypass inductance on distance protection. An improved setting method of distance protection for the SSFCL-equipped transmission line is proposed. Simulation study further demonstrates that the proposed method can effectively eliminate the unwanted effect of SSFCL on distance protection.
What problem does this paper attempt to address?