Improving performances of distance protection for centralized DFIG wind plant using the resistive-type SFCL

Yunzhu Cao,Chao Li,Meng Song,Li Li,Bin Li
DOI: https://doi.org/10.1016/j.seta.2024.103724
IF: 7.632
2024-03-05
Sustainable Energy Technologies and Assessments
Abstract:With increasing penetration of double-fed induction generators (DFIGs) capacity in the grid, the fault characteristics of the grid have also changed. During faults, the fault current of power grid has the characteristics of frequency offset under high penetration of DFIG wind plant, which can deteriorate the reliability of distance protection. Thus, this study focuses on the utilization and assessment of the resistive superconducting fault current limiter (SFCL) to mitigate effects of frequency offset on distance protection of centralized DFIG wind plant. There is a resistive-type SFCL to be utilized in the centralized DFIG wind plant to mitigate frequency offset that is caused by rotor frequency component of fault current. Moreover, the impacts of the resistive-type SFCL on instantaneous distance protection of centralized DFIG wind plant are evaluated under different types of faults. Finally, the DFIG wind plant with rated capacity of 93 MW is built in RTDS platform, and a 10 Ω resistive-type SFCL is utilized in the 35 kV transmission lines of DFIG wind plant. The tested results have validated that the SFCL with 10 Ω resistance can effectively mitigate the frequency offset of DFIG wind plant and enhance the reliability of phase-comparison distance protection in the 220 kV transmission lines.
energy & fuels,green & sustainable science & technology