The Principle of Transformer Differential Protection Based on Wave Comparison

he benteng,xu xidong
DOI: https://doi.org/10.3321/j.issn:0258-8013.1998.06.004
1998-01-01
Abstract:A new principle of transformer differential protection is presented in this paper.According to comparing the area,the wave of the transformer differential current can be divided to two parts.Based on their correlation and covariance,the criterion to distinguishing magnetizing inrush is made up.Computer emulation and dynamic simulation show,the protection can clear the close onto fault quickly and don not influenced by CT saturation.The protection action time is less than 15ms.
What problem does this paper attempt to address?