Influence of Sympathetic Interaction Between Transformers on Relay Protection

ZHANG Xue-song,HE Ben-teng
DOI: https://doi.org/10.3321/j.issn:0258-8013.2006.14.003
2006-01-01
Abstract:The principle of sympathetic interaction is analyzed firstly, which indicates that the bias flux is the primary factor in the produce process of sympathetic inrush. Then based on the simulation and combined with the characteristics of sympathetic interaction, we make a systematic study on the infection to the differential protection, back-up protection and other relative protection in the parallel connection and the series connection. The analysis shows that the saturation of current transformer caused by sympathetic inrush would bring some difficult in identifying the inrush in series connection; Moreover, it has great effect on the zero-sequence over-current protection of transformer and the back-up protection of the element in high level, such as over-current protection. The unit to identify inrush base on the harmonic restraint should be added to the protection.