Application of Equivalent Instantaneous Inductance in Nonstaturation Zone to Identify the Sympathetic Inrush in Transformer

BI Da-qiang,SUN Ye,WANG Xiang-heng,WANG Wei-jian
2008-01-01
Abstract:The sympathetic inrush may cause the mal-operation of differential protection for running transformer, and affect its normal running. However, there is no available effective measure to identify the sympathetic inrush at present. In this study, according to the cause of sympathetic inrush occurring and the characteristic that the equivalent instantaneous inductance of transformer can reflect its running situation, using the average of equivalent instantaneous inductance in non-saturation zone detects the sympathetic inrush, further blocks the differential protection and prevents it from mal-operation. The simulation and experimental results verify that the method have higher reliability than second harmonic restraint scheme against initial and third harmonic block scheme against saturation of current transformer, and have better immune to the saturation of current transformer. This work is supported by National natural Science Foundation of China (No. 50507014), in part by the Electrical Power Science and Technology Foundation of Xuji and in part by the Youth Innovation Foundation of the department of Electrical Engineering, Tsinghua University.