A novel equivalent instantaneous inductance based algorithm used to distinguish inrush currents for transformers

葛宝明,于学海,王祥珩,苏鹏声,王维俭
DOI: https://doi.org/10.3321/j.issn:1000-1026.2004.07.010
2004-01-01
Abstract:Distinguishing magnetizing inrush currents from internal faults can be effectively fulfilled by using the criterion of an instantaneous excitation inductance and an equivalent instantaneous inductance, which is based on the difference of the magnetic permeability in iron core of transformer between inrush currents and internal fault. However, existing methods cannot accurately obtain the equivalent instantaneous inductance because the large computational error greatly influences the accuracy of the criterion above. Therefore, an advanced computational method considering the equivalent resistance is proposed in this paper to calculate the equivalent instantaneous inductance. It greatly improves the computation accuracy. Two methods in time and frequency domains are further presented in the paper to distinguish inrush currents from internal faults based on the proposed method. Discussions to compare the proposed novel method and existing ones through experimental tests are given. The results show that the proposed method can provide more accurate calculation results and enhance the accuracy of the criteria in time and frequency domains.
What problem does this paper attempt to address?