Identification of Magnetizing Inrush for Three-phase V/V Traction Transformer

FENG Cun-liang,GE Bao-ming,BI Da-qiang
DOI: https://doi.org/10.3969/j.issn.1001-8360.2011.06.007
2011-01-01
Abstract:The key issue of traction transformer differential protection is to distinguish magnetizing inrush from internal fault current.The algorithm based on the equivalent instantaneous inductance can reflect the essential characteristic of the traction transformer operating conditions and distinguish magnetizing inrush from internal fault current correctly.For the three-phase V/V traction transformer,the connection is different and the operating circumstance is much worse than power transformers,and the second harmonic restraint scheme can not restrain effectively.At present,the equivalent instantaneous inductance based algorithm is still not applied to the three-phase V/V traction transformer to recognize magnetizing inrush from fault current,even though it is popular in application to the power transformers.This paper improved the applied conditions and the arithmetic elements to calculate the average equivalent instantaneous inductance in the none-saturation zone of differential currents,and applied the improved algorithm to distinguish magnetizing inrush from fault current.Dynamic experiments verified that the algorithm can distinguish the magnetizing inrush current and turn-to-turn fault current reliably and be immune to saturation of current transformers.