Analysis on the Influence of Series Sympathetic Inrush on the Differential Protection of Traction Transformers

FENG Cunliang,BI Daqiang,GE Baoming
2011-01-01
Abstract:The physical mechanism of series sympathetic inrush between two traction transformers in traction substation is introduced by the relationship between magnetizing voltage and magnetizing current.The influence of series sympathetic inrush on the differential protection is also analyzed.Due to the particularity of power supply mode,the initial inrush caused by the energized transformer running across the system resistance results in the non-periodic fluctuation of voltage in the common node.The distorted voltages cause series sympathetic inrush.The DC component in the series sympathetic inrush causes the saturation of current transformer which is the main reason of the mal-operation in differential protection for traction transformer.Dynamic experiments show that a restraint criterion based on compositive harmonic content can not recognize series sympathetic inrush efficiently.A criterion of current transformer saturation detection or the current transformers that are not prone to saturate is recommended.
What problem does this paper attempt to address?