MAGNETIC RESTRAINING DIFFERENTIAL BUS PROTECT

ma yongsheng,he benteng
1998-01-01
Abstract:Saturation of Current Transformer (CT) is the major problem of Bus Protect in power system.Many measures have been adopted to prevent CT from error operation after saturation,but until now this problem has not been satisfactorily solved for various reasons.On the basis of the physical principle of CT saturation,this paper present a new saturated criterion depending on the flux of CT,and find out a dependable measure to solve the error operation of Differential Bus Protect Coursed by CT saturation theoretically.Furthermore,a Differential Bus Protect technique based on the linear section of CT is presented.
What problem does this paper attempt to address?