Infulence of Current Transformer Saturation on the Distance Protection

黄莉,何奔腾
DOI: https://doi.org/10.3969/j.issn.1674-3415.2004.12.005
2004-01-01
Abstract:Through digital simulation tests with ATP, this paper studies the variation of the measured impedances in the Fourier algorithm-based distance protection, under the saturation of current transformer (CT). Research results show that the saturation of CT may probably result in the transcendence of the distance relays employed in the transmission lines. When the CT undergoes different saturation, the starting time, duration time and severe degree of the transcendence are also discussed in detail.
What problem does this paper attempt to address?