Research on the Practicality of Current Transformer Saturation Detection Using the Magnetic Restraint Principle

HUANG Zhi-yuan,HE Ben-teng,ZHANG Xue-song
DOI: https://doi.org/10.3321/j.issn:1000-1026.2006.04.015
2006-01-01
Abstract:An improved criterion using the magnetic restraint principle for detecting current transformer (TA) saturation combined with some characteristics of the second current is proposed for the equivalent circuit of TA. Hence the problem of obtaining the initial remanence is resolved in the core when the flux linkage is calculated using an integral algorithm. Simulation results with EMTP show that the improved criterion can accurately detect nearly all kinds of TA saturation and avoid mal-operation due to the remanence. In addition, the method is easy to implement and its validity and stability are satisfactory.