ANALYSIS AND COUNTERMEASURE FOR MISOPERATION OF LONGITUDINAL DIFFERENTIAL PROTECTION WITH UNCLEAR REASON

Wang Weijian,Li Fuying
DOI: https://doi.org/10.3321/j.issn:1000-1026.1999.18.005
1999-01-01
Abstract:Longitudinal differential protections for electric main equipments (transformer, generator, motor, busbar, etc. ) misoperate frequently under normal operation, and the same misoperation occurs over and over again. "Cause is not clear" is often the conclusion. This paper analyzes the transient performance of current transformer in the protective level. It is pointed out that TP class current transformer is too expensive for medium and low voltage device, and also difficult to install because of its bulky size. Digital optical current transducer (DOCT) has been developed successfully, which provides possibility to solve the said problems.