DISCUSSION ON SOME PROBLEMS EXISTING IN THE MAIN EQUIPMENT PROTECTION

王维俭,桂林,王祥珩
DOI: https://doi.org/10.3321/j.issn:1000-1026.2001.23.015
2001-01-01
Abstract:It is widely concerned how to avoid maloperation caused by the P class current transformer in external faults and other transient processes, which is generally applied in the main equipment protection. Taking 0.05I gn as the setting of the single element transverse differential protection, which is recommended in the guide rule. the maloperation has happened during a complete loss-of-field fault in the Ertan Plant. so an increase of 10% on the setting is suggested. This Paper also expands following subjects: The problem of logic product gate output which consists of loss-of-field protection criterions both in the system and the unit, selection of resistance value when the neutral point of large generator grounds through grounding transformer. Cancellation of rotor double ground protection, problems resulted from switching on without load for the phase-to-phase differential protection of transformer and the recommendation of zero-sequence differential protection, necessities of backup impedance protection and the accidental false switch on protection, etc. Some advice are put forward.