INVESTIGATION OF TURN-TO-TURN FAULT RATIO AND QUANTITATIVE DESIGN OF MAIN PROTECTION CONFIGURATION SCHEME FOR LARGE-SIZED TURBO-GENERATOR

桂林,王祥珩,王剑,孙宇光,王维俭
DOI: https://doi.org/10.3321/j.issn:1000-1026.2004.17.015
2004-01-01
Abstract:Owing to existence of the turn-to-turn fault of a large-sized turbo-generator stator winding in practice, harmful results can be caused without the turn-to-turn short-circuit protection in the operational mode. The turn-to-turn fault ratio of large-sized turbo-generators at home and abroad are reviewed. By the quantitative design of the main protection configuration scheme for two 300 MW turbo-generators, the necessity of leading out two neutral points and installing the branch current transformer at the neutral-point side of a turbo-generator is proposed. And high quality protection performances can be supplied by the transverse differential protection and incomplete longitudinal differential protection for the large-sized turbo-generator. To implement above configurations in practice need fully efforts of relay engineers, owners and machinery workers.