Study on New Leading-out Mode of Neutral Points of Large Turbo-generator

Weijian Wang
2006-01-01
Abstract:To provide overall protection to large turbo-generators, a new approach about leading-out mode of neutral points and disposition of protection schemes is presented. There are three terminals at the neutral point in most large generators. Complete longitudinal differential protection is the most commonly used method for stator winding protection, although it can not detect turn-to-turn faults in a same phase since there is no difference in the current entering and leaving the phase winding. To improve protection performance, it is necessary to lead out four or six terminals at the neutral point of large turbogenerators. However this can cause great changes of electrical machine design and manufacture. To solve this problem, the paper suggests that the second branch of phase A and that of phase B are led out and equipped with current transformer in the new leading-out mode. In addition, the first branches of three-phase and the second branch of phase C are connected to form the third leading-out terminal. By doing so, the incomplete longitudinal differential protection of phase C is different from that of phase A and phase B. To examine the sensitivity of the new protection scheme, two turbo-generators of 300 MW are simulated using the proposed multi-loop method. Simulation results indicate that the performance of the new protection scheme is much better than that of the traditional protection.