Review and Prospect of Main Protection Design for Hydro - Generators of Three Gorges Power Station

WANG Wei-jian,GUI Lin,SUN Yu-guang,WANG Xiang-heng
2006-01-01
Abstract:By summarizing the engineering experiences of Three-Gorges Left Bank Power Station, the main protection configuration scheme for hydro-generators of Three Gorges Right Bank Power Station is acquired through overall internal fault simulation and quantitative design process to satisfy the protection performance. Based on the primary configuration of one kind of transverse differential protection and one kind of longitudinal differential protection composed of complete split-phase transverse differential protection and incomplete or complete longitudinal differential protection, the calculated results act as a criterion whether the zero-sequence current transverse differential protection is accepted or not, thus determining the final main protection configuration scheme. Above quantitative and optimum design process will be verified and improved by a series of other large-sized generators with even branches. It is helpful to supply reliable assurance for the safe operation of large generators.