Rational Simplification of Quantitative Design Process of Main Protection for Large-sized Hydro-generator

GUI Lin,WANG Weijian,SUN Yuguang,WANG Xiangheng
DOI: https://doi.org/10.3321/j.issn:1000-1026.2007.04.021
2007-01-01
Abstract:With the main protection designs of seven hydro-generators in Three Gorges Right Bank, Longtan, Xiao wan, Goupitan, Jinanqiao, Laxiwa and Pengshui power stations as examples, the design process of hydro-generators with even or odd branches can be reduced to the main protection design of hydro-generators with two or three branches per phase and the branches per phase are reasonably grouped according to the possible fault features of different hydro-generators, such as adjacent or alternating modes. The summary of corresponding design rules directs the quantitative design for main protection configuration scheme, which greatly reduces the computation workload.
What problem does this paper attempt to address?