Optimum Design of Main Protection Configuration Scheme for Internal Faults of Generator with Even Multi-branches

SUN Yu-guang,WANG Xiang-heng,GUI Lin,WANG Wei-jian
DOI: https://doi.org/10.3321/j.issn:1000-1026.2005.12.017
2005-01-01
Abstract:By analyzing two kinds of typical internal faults of whose sensitivity is mostly affected by the concrete constitute manner of main protection in multi-branch generator, two principles for grouping the branches are presented in order to reduce the relative dead region. According to the two principles, the branch combination modes are determined directly from many choices without calculating the sensitivities, and the optimal protection configuration scheme with the maximum protection range is worked out through limited workload in Goupitan, Longtan and Zipingpu generators. Analysis results indicate that two-group branches scheme should be primarily considered for main protection configuration of even multi-branch generators.