Design of main protection configuration scheme for hydro-generator

Lin GUI,Xiang-heng WANG,Qun-gang ZHANG,Yu XI
DOI: https://doi.org/10.3969/j.issn.1006-6047.2007.02.002
2007-01-01
Abstract:Taking the quantitative design of main protection for Laxiwa hydro-generator with seven branches per phase as an example, differences between the design for hydro-generator with odd branches and that for even branches are pointed out. The incomplete split-phase transverse differential protection should be used first to abandon one branch per phase according to possible fault features of different hydro-generators and the left even branches per phase are reasonably grouped at adjacent or alternating mode. The composition of zero-sequence current transverse differential protection is then rationally selected to supplement the protection performance to incomplete split-phase transverse differential protection without additional hardware investment. The quantitative and optimum design will be verified and improved during its practices in large-sized hydro-generators with odd branches.