A comprehensive survey of the main protection scheme for three gorges hydraulic power plant generator No.1 at internal faults

Wei-jian WANG,Lin GUI,Xiang-heng WANG,Xue-shen ZHANG
DOI: https://doi.org/10.3969/j.issn.1674-3415.2001.01.008
2001-01-01
Abstract:For phase-to-phase and turn-to-turn S/C, analysis and calculation added up to 11490 faults have been made for Three Gorges hydraulic power plant generator No.1, combined with simple element transverse differential protection, split-phase transverse differential protection, incomplete and complete longitudinal differential protection. Based on sensitivity calculation, the main protection scheme of internal faults for this generator is proposed in this paper.
What problem does this paper attempt to address?