Calculation and analysis for incomplete differential protection of large water turbo generators

Weijian Wang,Junhong Liu,Ninghai Meng
1994-01-01
Abstract:The multi-loop method was adopted to calculate the inner fault currents of domestic large water turbo generators in this paper. Based on the results of calculation, the differential protection scheme for Er Tan's generators was discussed, which was proposed by one foreign consulting company. Through analysis, it was proved that the scheme has the advantage of simplicity, but for certain internal faults, it may reject to respond. So for the large water turbo generator with multi-branches, this incomplete differential protection must be used with cautions.