Research on the Main Protection Configuration Scheme for Internal Faults of Longtan Generator

孙宇光,王维俭,桂林,王祥珩,朱义军,李正茂
DOI: https://doi.org/10.3321/j.issn:1000-1026.2005.01.020
2005-01-01
Abstract:The final main protection configuration scheme for internal faults of large generators should be determined by means of quantitative design. Since a multi-branch hydro-generator could adopt many modes of neutral-point lead, its main protection configuration has a large number of constitute manners and compound schemes. Hence it is extremely difficult to find the optimal protection scheme for large generators with multi branches, such as Longtan Generator, by enumeration method. When the characteristics of stator windings and internal faults of Longtan Generator are analyzed, it is found that the dead region could be deduced by right choice of the mode of neutral-point lead. Through quantitative design, a protection configuration scheme with the largest protection range and higher degree of double-protection is presented in this paper, which can be easily realized in fields.