New Development of Protection Technique for Electric Main Equipment

王维俭,王祥珩,桂林,孙宇光
DOI: https://doi.org/10.3969/j.issn.1674-3415.2004.01.001
2004-01-01
Abstract:The design and setting of main protection for large-sized generator and extra-high voltage transformer aren't sufficiently based on the scientific simulation of stator winding internal faults at home and aboard. In most cases, the designers work on the project only by their own judgment and experience, along with outdated technology materials. The main protection design for generator and transformer should be quantitative and scientific after the internal faults simulation software has passed the State verification. The impedance protection isn't suitable for short-range backup protection for the winding faults of the large-sized generator and transformer. The specific status that the zero-sequence differential protection is seldom adopted at the stator winding of extra-high voltage transformer ought to be modified in China.