Discussion about Settings Checking of Ground Fault Protection from Two External Ground Faults

Jin-tao LIU,Da-qiang BI,Jun QI,Chun-yu REN
DOI: https://doi.org/10.3969/j.issn.1674-3415.2005.21.005
2005-01-01
Abstract:As one of important protections,the principle and settings of zero-sequence fundamental voltage protection are simple and easy.However,the requirement of checking ground fault protection is not clearly described in the guide of relay protection setting,it is not benefit to the settings of protection in practice.By analyzing two external faults causing the maloperation of ground fault protection,this paper represents the necessity and method of checking the setting value of zero-sequence fundamental voltage in ground fault protection for generators.