Preventing the Generator Stator Ground Protection from Maloperation Caused by the Secondary Ground Fault of High Voltage Station Transformer

王维俭,毕大强
DOI: https://doi.org/10.3969/j.issn.1006-6047.2001.09.001
2001-01-01
Abstract:The large-sized generator ought to install the ground fault protection based on the zero-sequence fundamental voltage (3U 0)with the setting value not less than 5 V.But in the field operations,The 6 kV station service electrical system took place single-phase-to-ground faults reaulted in the zero-sequence fundamental voltages of generator reaching to 13.2 V and 11.9 V respectively,and the stator ground protection maloperated.Its reason lies in the zero-sequence transferring voltage caused by the coupling capacitance between primary and secondary windings of high voltage station transformer,which was not considered.The value of operating voltage 3U 0 should be set by calculation according to the transformer voltage,or the 3U 0 ground fault protection should extend the zero-sequence voltage of the station service electrical system as the restraint quantity for obtaining the operating dead-zone not more than 5%.