TRANSIENT ANALYSIS ON LARGE HYDRO-GENERATOR WITH HIGH RESISTANCE GROUNDING

张琦雪,王祥珩,王维俭
DOI: https://doi.org/10.3321/j.issn:1000-3673.2004.01.008
2004-01-01
Abstract:To calculate and analyze the transient over-voltages and the fault current accurately during the stator intermittent arc grounding, a multi-loop model with quasi-distributed capacitances is presented with which the influence of the distributed capacitances and the harmonic magnetic field in air gap can be more accurately taken into account. On this basis the calculation for a large hydro-generator in the Three Gorges Power Station is carried out and the calculation results show that when single phase to ground fault occurs in stator winding under the high resistance grounding of the generator neutral and the value of neutral resistance is high, only finite fault current can be reduced, and a higher transient over-voltage may occur. When the fault current and the transient over-voltage are synthetically considered, it may be proper that the value of neutral resistance should be 2 to 3 times of that of neutral point equivalent capacitive reactance. If the frequency of the generator deviate from its normal value, the higher transient over-voltage may occur.