PROTECTION SCHEME BASED ON FAULT TRANSIENT COMPONENT OF THIRD HARMONIC VOLTAGE FOR STATOR GROUND FAULT OF GENERATORS

毕大强,王祥珩,王维俭
DOI: https://doi.org/10.3321/j.issn:1000-1026.2003.13.010
2003-01-01
Abstract:This paper puts forward a transient based protection scheme for the stator ground fault of generator. The fault transient component of third harmonic voltage at neutral is approximately equal to that at terminal. Choosing their sum and difference as the action and restraint signal respectively, the protection detects the ground fault by comparing the spectrum energy of action and restraint signals. The results of simulation and experiment verify the novel protection scheme is with high sensitivity, is immune to the operating condition of generator, and is of robustness.