Detecting the PT Secondary Circuit Open at the Neutral of Generator

毕大强,王祥珩,王维俭
DOI: https://doi.org/10.3969/j.issn.1674-3415.2004.16.009
2004-01-01
Abstract:This paper analyses the effect of PT secondary circuit open at the neutral on the stator ground protection, and points out that this kind of PT fault will cause the maloperation of the stator ground protection, which adopts the ratio of third harmonics. However, it is hard for the present method to detect the PT secondary circuit open at the neutral. In the paper, the variations of the fault components of third harmonic at the terminal and neutral, which are nearly the same, are used to distinguish faults between the PT secondary circuit open and the direct grounding at the neutral to prevent the stator grounding protection from maloperation.