PROTECTION SCHEME BASED ON THE FAULT TRANSIENT COMPONENT OF ZERO-SEQUENCE VOLTAGE UNDER THE STATOR GROUND FAULT OF GENERATORS

毕大强,王祥珩,桂林,王维俭
DOI: https://doi.org/10.3321/j.issn:0258-8013.2003.11.009
2003-01-01
Abstract:This paper puts forward two kinds of transient based protection scheme for the stator ground fault of generators in terms of the feature that the fault transient component of zero-sequence voltage at the neutral is approximately equal to that at the terminal. In the first kind of scheme, the fault transient components of fundamental frequency and third harmonic voltages are calculated respectively. In the second kind of scheme, the sum and difference of fault transient components at the neutral and the terminal are directly chosen as the action and restrain signals, and then their spectrum energies are compared to detect the ground fault. The simulation and experimental results of the latter scheme are given. The results verify that the proposed transient based protection is with high sensitivity and reliability.