Application of injecting 20Hz source-based stator ground fault protection for generators in expanded unit connection

LIU Chun-qiu,GE Bao-ming,BI Da-qiang
DOI: https://doi.org/10.3969/j.issn.1674-3415.2011.03.008
2011-01-01
Abstract:At present,the stator ground fault protection of generator through injecting 20 Hz voltage cannot be used in generators connected to expansion units due to lack of selectivity.This paper proposes an improved protection scheme to realize the selectivity. The proposed scheme firstly calculates the ground resistance value of generators to determine whether ground fault occurs. When the ground fault is detected,the 20Hz differential current between the neutral and terminal of each generator can be obtained .The phase relationship between the 20Hz differential current and injected 20 Hz voltage is derived.The new protection scheme can determine the fault generator according to the phase relationship,so that it can achieve a selective shutdown.The simulation results verify the accuracy of calculating the grounding transition resistance and selecting the fault generator,whichrealizes the application of the injecting stator ground fault protection in the generators connected to expanding units.