DEVELOPMENT OF A HIGH ACCURACY STATOR GROUND FAULT PROTECTION BY INJECTING 20 Hz VOLTAGE

毕大强,王祥珩,余高旺,李德佳,王维俭
DOI: https://doi.org/10.3321/j.issn:1000-1026.2004.16.017
2004-01-01
Abstract:This paper analyzes the effect of parameters of distribution transformer at the neutral on the stator ground fault protection by injecting 20 Hz voltage. Based on the hardware platform of the Xuji WFB-800 generator-transformer unit protection, a high accuracy stator ground fault protection is developed by considering above parameter effects. The experimental results verify the method of calculating the grounding transition resistance. And some measures are given to prevent mal-operations caused by the failure of 20 Hz voltage and its lead line.