Application of Ground Insulation State to Improve Ground Fault Protection Using Third Harmonic Voltage for Huge Hydraulic Generator

DANG Xiaoqiang,TAI Nengling,LIU Junyong,ZHANG Li,FENG Zhe
DOI: https://doi.org/10.13334/j.0258-8013.pcsee.2012.34.018
2012-01-01
Abstract:Huge hydraulic-generators usually install two-frequency 100% protection for single-phase ground short faults,but the reliability,sensitivity and simplicity of its third-order harmonic voltage protection are not ideal in actual application.This paper presented a protection scheme to resolve these problems based on insulation condition principle.The principles of third-order harmonic voltage protection for ground faults were discussed,and its maloperations caused by generator starting,tripping and changes of operation modes were analyzed.The principle based on neutral side insulation condition was introduced and its keystone is to change the protection criterion based on the difference of electrical quantities to the nondimensional impedance ratio protection criterion based on insulation condition.Combining the principle and the characteristics of the ground faults,the effect in solving the existing problems was analyzed and the results indicate that the criterion is feasible and is hopeful in improving the performance of the ground fault protection for hydraulic-generators.