Research and improvement of stator grounding protection based on third-harmonic voltage for large-scale turbine generator

Jianbin SANG,Minglei BAO,Yuping LI,Ming LI,Yerong XU
DOI: https://doi.org/10.16081/j.issn.1006-6047.2017.10.027
2017-01-01
Abstract:The sensitivity of three common stator grounding protection schemes based on the third-harmonic voltage is compared and analyzed based on the parameters of a 300 MW turbine generator,which shows that the sensitivity of stator grounding protection schemes may be insufficient in the middle of the stator winding if the turbine generator is connected with the grounding transformer.Considering the frequent maloperation present in the existing stator grounding protection schemes based on the third-harmonic voltage,the causes of third-harmonic voltage variation of the generator terminal and the generator neutral point are analyzed.Based on the above research,an improved stator grounding protection scheme based on third-harmonic voltage variation component differential principle is proposed.The variation of the third-harmonic voltage of the generator terminal are corrected and then adopted to construct the differential criterion with the variation of the third-harmonic voltage of the generator neutral point,which can effectively distinguish the stator grounding faults from the normal change of generators' third-harmonic voltage.In order to avoid false tripping caused by harmonic voltage changes at high voltage side,a floating threshold value is also set according to the variation of the third-harmonic voltage at high voltage side.Simulative results show that the proposed scheme is theoretically correct and slightly affected by the changes of generator operating state with high sensitivity.
What problem does this paper attempt to address?