TRANSIENT SIMULATION FOR THE STATOR GROUND FAULT OF LARGE-SIZED HYDRO-GENERATOR

毕大强,王祥珩,王善铭,王维俭
DOI: https://doi.org/10.3321/j.issn:1000-1026.2002.15.008
2002-01-01
Abstract:Considering the actual structure of stator and rotor windings, this paper presents a new transient simulation model for the stator ground faults of hydro-generator based on the calculation of the inductance parameters of windings by using the multi-loop theory. Taking a design for Three Gorges generators as an example, the paper analyzes the effects of distributed stator ground capacitance on the model. The relationship between zero-sequence voltage at the generator terminal and its neutral and the ground fault position and ground resistance are discussed, the characteristics of ground fault current as a function of ground fault position and ground resistance are also presented. The model can simulate the whole process of stator ground fault well. The simulation results will provide guidelines for the relay protection checking and new protection scheme development.